Texas State Fire Marshal Rules (28 TAC Chapter 34, Subchapters C, E, F and G)

42 controls. 0 other frameworks in our corpus share controls with it. Here is all of it, and how much of it you are already doing.

Page built . This page is derived from the framework corpus, which changes when the corpus is extended rather than daily.

42 controls 0 frameworks share controls with it United States (Texas) verified against its source document

Every control below is one this framework asks for. The right hand column counts how many other frameworks in our corpus carry the same control, which is the difference between doing this work once and doing it again for the next standard.

There is no implementation kit for this framework yet. The control list and the overlap above are free and complete.

What you already have

Frameworks whose controls overlap this one, most first. If you run any of them, the count is roughly what you have already evidenced.

No measured overlap with another framework in the corpus.

Every control

CodeControlAlso in
34.303Buildings inspected by the state fire marshal are judged against NFPA 1 and NFPA 101 with the stated carve-outs0
34.320Inspection priority for state buildings follows the published potential fire safety risk factors0
34.340Requested fire safety inspections use the prescribed form and attract the scheduled fee by building type0
34.510-a-dFire extinguisher firms and branches hold a certificate of registration, employ a licensed person, keep a physical business location and a Type C registration for DOT cylinder test0
34.510-eMaintain a properly equipped shop for the extinguishers and systems the firm services0
34.511Extinguisher licence types, proof of licensure, revised licences, employment by a registered firm and the six-month prerequisite for Type A and K0
34.512Apprentice permits: proof carried, changes notified within 14 days, non-transferable, work only under direct supervision0
34.516Licence examinations: 70 percent pass mark, content by licence type, retests, three attempts a year and the one-year application window0
34.517-aPortable extinguishers installed and serviced to the manufacturer's instructions and the adopted standards, with a service tag on completion0
34.517-bFixed extinguisher systems planned, installed and serviced to manual or standard, with the certifying licensee present at the final test and an installation label and service tag a0
34.518Shop drawings and hydraulic calculations for engineered fixed systems delivered to the owner, kept for the life of the system and signed by a Type PL licensee0
34.519Installation labels and installation certificates for fixed extinguisher systems0
34.520Service tags on portables and fixed systems: content, size, colour, placement and who may remove them0
34.521Red tags for unsafe or inoperable extinguishers and systems, with immediate owner notice, AHJ notice within 24 hours and three business days, and notice of correction within five0
34.604Exempt persons still plan and install fire alarms to the adopted standards0
34.607Fire alarm work follows the adopted NFPA standards and the National Electrical Code as listed0
34.610Fire alarm firms: physical business location, a full-time designated licensed employee, marked vehicles, ownership and officer changes reported, branch certificates0
34.611Fire alarm licence and approval types, proof carried, changes and employment events reported within 14 days0
34.615Fire alarm licence examinations on the rules, the statute and a technical qualifying test0
34.616Sales, installation and service: supervised exempt staff for single-station residential alarms, licensed on-site supervision, certifier present at acceptance, cross-licensing and t0
34.617Installation certificate for every non-residential installation, modification or addition, distributed to site, firm file and AHJ within ten days0
34.618Three staged installation inspections by a licensed technician or planner, documented on the inspection form, with the AHJ told if corrective action lags ten days0
34.619Plans by a licensed planner or professional engineer, signed and stamped, record drawings to the owner, nothing stored in panels, residential drawings kept a year0
34.620White installation labels inside the panel cover after new, extended or altered systems, naming firm, licensee and planner0
34.621White service labels after every service, layered to keep a history, with yellow or red labels and notices where the system is deficient0
34.622Blue inspection and test labels after each inspection, applied to new systems only after AHJ acceptance, kept five years0
34.623Yellow labels for non-compliant fire alarm systems, with written notice to owner and AHJ within five business days and notice when corrected0
34.624Red labels for inoperable, faulted or impaired fire alarm systems, with oral notice at once and written notice within one or three business days0
34.627-34.628Approved training schools and instructors for residential fire alarm technicians, and the seven-hour minimum curriculum0
34.707Sprinkler work follows the adopted NFPA installation and ITM standards0
34.710Sprinkler contractors hold a certificate of registration of the right type, never subcontract to unregistered firms, post the certificate and report changes0
34.711Responsible managing employees licensed by type, carrying proof, employed by a registered firm, with changes and departures reported within 14 days0
34.715RME examinations: 70 percent pass on the rules and the statute plus any technical qualifying test, retests and re-examination after two years' lapse0
34.716Installation under the right RME, contractor's material and test certificate distributed three ways, ITM by licensed inspectors, complete service records and marked vehicles0
34.717As-built plans and hydraulic calculations to the owner, kept for the life of the system, updated for alterations above twenty sprinklers, signed and stamped by the RME0
34.718Durable white installation tags on every riser recording the water supply test data, kept for the life of the system, plus an ITM tag after initial tests0
34.719White service tags on each riser after every service, with yellow or red tags where deficiencies or impairments exist, kept five years0
34.720Light blue ITM tags after each inspection, testing and maintenance visit, recording the type, status and main drain pressures, kept five years0
34.721Yellow tags for non-compliant, unmaintained or recalled-equipment sprinkler systems short of an emergency impairment, with written notice within five business days0
34.722Red tags for emergency impairments under NFPA 25, with immediate oral notice and written notice within 24 hours to owner and AHJ0
P1What Chapter 34 is, how it is adopted and what this framework models0
P2Definitions, approved laboratories and testing organisations, fees, applications, enforcement and savings clauses0

Tell me when Texas State Fire Marshal Rules (28 TAC Chapter 34, Subchapters C, E, F and G) files something new

One email when a public company newly discloses something this framework governs, naming the company and what our corpus says it puts in scope. Nothing else, and one click to stop.

What this page is

A control-level reference for Texas State Fire Marshal Rules (28 TAC Chapter 34, Subchapters C, E, F and G), drawn from our framework corpus. Control codes and titles are references to the standard, not reproductions of it. The overlap counts and the auditor artefacts are our own work and are the part you will not find elsewhere.

Measure this against what you already run · All frameworks · Today's edition