1-3 | Scope, references and terms | 0 |
4.1 | Define the class for one or more occupancy states | 0 |
4.2 | Choose the threshold particle size or sizes within the permitted range | 0 |
4.3 | Designate the class by its ISO Class number using the limit table | 0 |
4.4 | State the full designation: class, occupancy state and considered sizes, with a size ratio of at least 1,5 | 0 |
4.5 | Use Annex E for intermediate decimal classes and intermediate size thresholds | 0 |
5.1 | Verify compliance by specified testing and documentation, repeat by risk, and monitor under ISO 14644-2 | 0 |
5.2 | Test by the Annex A reference method, or an agreed equivalent, with calibrated instruments | 0 |
5.3 | Evaluate particle concentrations against the class limits at every location, by one method for all sizes | 0 |
5.4 | Issue a comprehensive test report with a compliance statement and the required contents | 0 |
A.2 | Use a discrete particle counter able to size and count at the required sizes, with a valid calibration | 0 |
A.3 | Confirm the cleanroom is complete and functioning to specification before counting | 0 |
A.4.1-3 | Derive the minimum number of sampling locations and position them representatively | 0 |
A.4.4 | Set the single sample volume and time per location from the class limit, at least 2 litres and 1 minute | 0 |
A.5 | Follow the sampling procedure: set-up and zero check, probe orientation, occupancy conditions, handling of abnormal counts | 0 |
A.6.1 | Record each sample count and calculate the average and the concentration per cubic metre at each location | 0 |
A.6.2 | Judge classification from the per-location averages and investigate any out-of-specification result | 0 |
B-F | Informative annexes: worked classification examples, macroparticles, sequential sampling, intermediate classes and test instruments | 0 |